Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

Version 1 Current »

Here is an example of how you can write a program to have the ACR9030/9040 automatically start the EPL network on powerup.

PROGRAM
PBOOT
...
PERIOD 0.001 : REM for Compax3EPL, PERIOD *must* be set to 0.001

INH 16648 : REM wait until EPL card is ready
EPLC ON : REM Turns on EPL Network. Same as SET 16640

REM loop until Network Start either failed or successful
WHILE NOT(BIT 16650 OR BIT 16649)
WEND

IF(BIT 16650) : REM Network start failed
GOTO NoEPL
END IF

REM Network is now operational.

...
[code]
...

_NoEPL
PRINT "EPL Network failed to start"
'[diagnostic stuff]
ENDP

  • No labels

0 Comments

You are not logged in. Any changes you make will be marked as anonymous. You may want to Log In if you already have an account.