This example shows some basic data exchanges between a Parker AC10 VFD drive and a Parker Interact Xpress XT HMI over Modbus/RTU and an RS485 connection.

See the AC10 Installation Guide for more details on its Modbus/RTU implementation (Chapter 12):

AC10 IP20 User Guide

AC10 IP66 User Guide

The specific Modbus/RTU settings in the Xpress application are as follows to match up the AC10 defaults pretty closely.

AC10-Modbus-Settings-1_3507-20240521-000845.JPG

The AC10 Modbus implementation limits 'block reads' to 10 registers or less.

AC10-Modbus-Settings-2_3508-20240521-000845.JPG

Tag address list for the Xpress project:

Xpress_to_AC10_via_Modbus-RTU_Tags.txtDownload

Name				 Address
OutputFrequency			 h401000
OutputVoltage			 h401001
OutputCurrent			 h401002
PoleNumbers_ControlMode	 	 h401003
BusVoltage			 h401004
DriveRatio_InverterStatus	 h401005
PercentOutputTorque		 h401006
InverterTemp			 h401007
ApplicationSelection		 h40021C
DI1Functions			 h400310
DI2Functions			 h400311
DITerminalStatus		 h40100B
TerminalOutputStatus		 h40100C
AI1Value			 h40100D
AI2Value			 h40100E
Motor_StatorResistance		 h400806
AO1Value			 h401015
AO2Value			 h401016
CurrentSpeed			 h401017
Motor_RotorResistance		 h400807
ControlValue			 h402000
DI3Functions			 h400312
DI4Functions			 h400313
DI5Functions			 h400314
DI6Functions			 h400315
DI7Functions			 h400316
DI8Functions			 h400317
Motor_AutotuneType		 h400800
Motor_RatedPower_kW		 h400801
Motor_RatedVoltage_V		 h400802
Motor_RatedCurrent_A		 h400803
Motor_NumberofMotorPoles	 h400804
Motor_RatedRotarySpeed_RPM	 h400805
Motor_RatedFrequency_Hz	 	 h40080A
TargetFrequency			 h40010D
DO1Functions			 h400301
DO2Functions			 h400302
FactoryReset			 h40013C
Motor_LeakageInductance	 	 h400808
Motor_MutualInductance		 h400809
RelayOutputFunctions		 h400300
DIActiveLevel			 h400328
AO1Functions			 h40041F
AO2Functions			 h400420
MainFrequencySource		 h400203

Example Xpress Manager project:

AC10 Modbus Example to Interact Xpress HMI.zip