This example shows some basic data exchanges between a Parker AC10 VFD drive and a Parker Interact Xpress XT HMI over Modbus/RTU and an RS485 connection.

See the AC10 Installation Guide for more details on its Modbus/RTU implementation (Chapter 12):

AC10 IP20 User Guide

AC10 IP66 User Guide

The specific Modbus/RTU settings in the Xpress application are as follows to match up the AC10 defaults pretty closely.

The AC10 Modbus implementation limits 'block reads' to 10 registers or less.

Tag address list for the Xpress project:

FullscreenXpress_to_AC10_via_Modbus-RTU_Tags.txtDownload

123456789101112131415161718
Name                 AddressOutputFrequency          h401000OutputVoltage            h401001OutputCurrent            h401002PoleNumbers_ControlMode      h401003BusVoltage           h401004DriveRatio_InverterStatus    h401005PercentOutputTorque      h401006InverterTemp             h401007ApplicationSelection         h40021CDI1Functions             h400310DI2Functions             h400311DITerminalStatus         h40100BTerminalOutputStatus         h40100CAI1Value             h40100DAI2Value             h40100EMotor_StatorResistance       h400806AO1Value             h401015

Example Xpress Manager project:

AC10 Modbus Example to Interact Xpress HMI.zip