Compax3 Troubleshooting - Feedback Resolver Too Low (Fault 0X7382)

Standard reaction for resolver level error is immediate switching off resolver excitation; so error quit is possible only by power off/on.

When resolver signal level is too low adjustment of signal level is also possible with

Resolver_ResolverLevelAdaption o280.3 = 100...200% (changes get valid immediately)

To check the feedback level, the optimization window can used to graph the resolver levels or monitored in the status display.

Status of actual resolver signal level:
StatusFeedback_ResolverLevel o692.9 = sin2 + cos2 (without square root)

StatusFeedback_FeedbackSineDSP o692.1 = sin (typ. 0.85 max)

StatusFeedback_FeedbackCosineDSP o692.2 = cos (typ. 0.85 max)

Switching resolver excitation off can be suppressed by
Resolver_ResolverDebug o280.2 = -1

 

 

Related FAQ:   Compax3 Software - C3ServoManager - How to View or Monitor any Object in Optimization (Activate Object Tree)

 