What Are the Basic Parameters to Run an AC Induction Motor from Just the Keypad?
To run an AC induction motor on the AC10 in a new application consult the Quickstart guide, on the product page for the AC10 on Parker.com - [Manual, QuickStarts, Product Support, etc].
Â
Below are the minimum parameters that need to be set to run an AC induction motor from just the keypad. Descriptions of these parameters can be found in the manual on the product page, at the link above. If you have already done some programming on the AC10 you can reset the drive to factory defaults by setting F160 = 1.
Â
Motor Data Parameters With Required Values:
F801 (Rated Power [kW]) = Motor Nameplate Value
F802 (Rated Voltage [V]) = Motor Nameplate Value
F803 (Rated Current [A]) = Motor Nameplate Value
F804 (Number of Motor Poles) = Motor Nameplate Value
F805 (Rated Rotary Speed [RPM]) = Motor Nameplate Value
F810 (Motor Rated Frequency [Hz]) = Motor Nameplate Value
Â
Control Parameters With "Keypad Only" Values:
F200 (Source of Start Command) = 0
F201 (Source of Stop Command) = 0
F203 (Main Frequency Source) = 0
F207 (Frequency Source Selecting) = 0
Â
Speed Parameters With Starter Values:
F106 (Control Mode) = 2
2 is V/Hz Mode
F111 (Max Frequency [Hz]) = F810
F113 (Target Frequency [Hz]) =Â [User Defined]
The drive ramps to this value when a RUN command is initially given. Set to [F810] for motor nameplate frequency.
F118 (Base Frequency [Hz]) = F810
Â