Updated Control Terminal Torque Specifications for AC10 VFDs

It has been determined that the AC10 control terminal torque specification of 0.6Nm in the product manuals for both the IP20 and IP66 (NEMA4X) versions is incorrect. The correct control terminal torque specifications are as follows:

           

IP20 Version  P/N’s beginning 10G-

           Frame 1                         0.2Nm

           Frames 2 & larger          0.4Nm

 

IP66 (NEMA4X) Version  P/N’s beginning 16G-

            All Frames                     0.4Nm

 

 

 

glh 9/2020